Single-Phase UPS (1-3 kVA) series

Purpose / Description
The UPS products provide power supply to computer systems and other equipment in case of supply voltage drop or interruption.
Performed functions
  • - Smoothing of short-time power surges;
  • - Supply voltage filtering, noise reduction;
  • - Reserve electric power supply after power drops;
  • - Detecting the emergencies and alarm signal generation (audio signals, start of external programs, etc.)
Features & Benefits
CapacityFullkVA123
ActivekW0.81.62.4
Voltage range Low voltage transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC 5% (based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low voltage recovery 168 VAC / 148 VAC / 128 VAC / 118 VAC 5% (based on load percentage 100% -80% / 80% -70% / 70% -60% / 60% -0)
High voltage transfer 300 VAC 5%
High voltage recovery 290 VAC 5%
Frequency range 40 Hz ~ 70 Hz
Power factor ≧ 0.99 @ normal voltage (full load)
Output voltage 200/208/220/230/240 VAC
Voltage range (battery mode)
Frequency range 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz
Frequency range (battery mode) 50 Hz 0.2 Hz or 60 Hz 0.2 Hz
Surge ratio 3:1
Harmonic distortion ≦ 2 % THD (linear load); ≦ 4 % THD (non-linear load)
Transfer time AC to DC 0
Inverter to bypass 4 ms (usual)
Battery model 12 V / 9 AH or 12 V / 7 AHUp to the Customer
Quantity, pcs. or 3
Standard charging time 4 hours to 90%
Max. charging current 1.0
Charging voltage 27.3 VDC 1% or 41.0 VDC 1%
LCD or LED
Battery mode
Low battery
Overload
Error
Capacity Full, kVA 123
Active, kW 0.81.62.4
Dimensions, D x W x H (mm) 38043888 48043888
Weight (kg) 10 -
Humidity 20-90 % RH @ 0- 40C (non-condensing)
Noise Less than 50 dBA @ 1 meter
Smart RS-232 / Optional USB Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Optional SNMP Support SNMP management and network management